How to Measure Multiple Load Cell / Strain Gauge Inputs – 8400915
Defining the Problem
Very often, load cells and strain gauges are remotely mounted away from a data collection device or a controller. In these
applications, converting these input devices to run on an Ethernet network is a better practice than hard-wiring over long
distances. For remote measurement, Acromag’s 962EN model for Modbus TCP/IP or Ethernet/IP can be used.
Both of these Acromag models measure a single load cell / strain gauge input or can be used to sum multiple inputs. In this
example, we are measuring multiple load cell inputs from a truck weigh station. Summing multiple load cells into the 962EN
will send a digital representation of the status of all inputs over Ethernet. A controller would receive the multiple inputs and
do the averaging.
System Requirements
The 962EN is a differential voltage input Ethernet module with many input ranges to select, from +/-78mV to +/-10V DC.
Each range is normalized to the output using a 16-bit A/D converter. This accuracy is maintained down to a maximum
input of 10% of the range selected. For the lowest range, +/- 78mV, the 962EN will have 16-bit accuracy with a full scale
input as low as +/- 8mV. To determine the full-scale output from the load cell, the equation is:
Output (mV) = Excitation (V) x Bridge Sensitivity or Gauge Rated Output (mV/V) x (Actual Maximum Weight / Load Cell
Capacity)
To get the best measurement resolution, use the smallest input range possible without having the maximum bridge output
voltage level exceed that range. For most strain gauges and load cells, the +/-78mV range will be appropriate.
Implementing the Solution:
A load cell or strain gauge requires an excitation voltage to power, or excite, the resistance bridge that is used to measure
the deflection, or “strain” on the cell. This deflection can be in compression (positive bridge output voltage) or tension (negative
bridge output voltage). The excitation power supply must be of very high quality; it must be isolated, well regulated,
and have very low output ripple in order to provide an accurate bridge output voltage. One example is the Acopian 10V
power supply, Model 10EB24.
As you can see from the equation above, if the excitation voltage fluctuates, then the output will change without any
change in the force. For remote measurement with the 962EN, it is important to use a highly stable power supply for the
Excitation source to the Load Cells.
If the supply is used to power several load cells or strain gauges, it must be capable of providing enough current output.
Load cell bridge impedances are typically 350 ohms, but this can vary. To sum 4 load cells, each 350 ohms, the total
impedance is 87.5 ohms. With a 10V excitation, the current required is 114mA. A 10V highly stable power supply with at
least this capacity should be selected.
Once the 962EN is configured, the input signal levels are read by the controller over the network. The voltage readings can
then be scaled and processed in the controller.
Featured Products:
962EN-4006 – Modbus TCP/IP, i2o
962EN-6006 – Ethernet/IP
Why Acromag:
Acromag is known in the Process industry for the accuracy and reliability of its products. Acromag’s Busworks 900EN series
products support a variety of network protocols such as Modbus TCP/IP, Ethernet IP, and i2o.
Download PDF for complete document.