TT233: Thermocouple / milliVolt Input Two-Wire Transmitter
Product short description:
- Universal TC type J, K, T, R, S, E, B, N or ±100mV input
- 4-20mA ouput (sink/source)
- 12-32 V DC loop/local power
The TT233 model is a space-saving two-wire transmitter that isolates and converts a millivolt or thermocouple sensor input to a proportional 4-20mA control signal. Power is received from the output loop current or a DC supply when using a three-wire connection.
Click here to watch a short AcroMaggie video highlighting the TT230 Series.
- Description
- Features & Benefits
- Tech Papers
- Specs & Data Sheets
- Software
- Accessories
- Additional information
The TT233 model is a space-saving two-wire transmitter that isolates and converts a millivolt or thermocouple sensor input to a proportional 4-20mA control signal. Power is received from the output loop current or a DC supply when using a three-wire connection. The transmitter performs thermocouple linearization, cold junction compensation, and lead-break detection.
High-voltage isolation separates the input from the output circuit. Isolation protects from surges, reduces noise, and eliminates ground loop errors.
Setup and calibration are fast and easy with a convenient USB connection to your PC and Acromag’s Windows configuration software.
Advanced signal processing capabilities, variable range input, and convenient USB programming make this instrument a very versatile temperature measurement device. These transmitters can withstand harsh industrial environments and operate reliably across a wide temperature range with very low drift. They feature RFI, EMI, ESD, EFT, and surge protection plus low radiated emissions.
Performance Specifications
IMPORTANT: To prevent damage or errors from grounded PCs and surges, Acromag strongly recommends the use of their USB-ISOLATOR when configuring a TT230 Series transmitter.
USB Interface
USB Connector: USB Mini-B type socket, 5-pin
USB Data Rate: 12Mbps. USB v1.1 and 2.0 compatible
USB Transient Protection: Transient voltage suppression on power and data lines
USB Cable Length: 5.0 meters maximum
Driver: Not required. Uses built-in Human Interface Device (HID) USB drivers of the Windows operating system
Input
Default Configuration/Calibration:
Input: TC J, -210 to 760°C, high filter, Break: up
Output: 4 to 20mA
Input Ranges and Accuracy
Input Range Accuracy
TC J -210 to 760°C (-346 to 1400°F) ±0.5°C
TC K -200 to 1372°C (-328 to 2502°F) ±0.5°C
TC T -260 to 400°C (-436 to 752°F) ±0.5°C
TC R -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC S -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC E -200 to 1000°C (-328 to 1832°F) ±0.5°C
TC B 260 to 1820°C (500 to 3308°F) ±1.0°C
TC N -230 to -1300°C (-274 to 2372°F ±1.0°C
mV -100 to 100mV ±0.1mV
Thermocouple Reference (Cold Junction Compensation): ±0.2°C typical, ±0.5°C maximum at 25°C
Ambient Temperature Effect: Better than ±80ppm/°C (±0.008%/°C)
Zero Scaling Adjust: 0 to 95% of range, typical
Lead Break (Sensor Burnout) Detection: Configurable for either upscale (24mA) or downscale (3.3mA) operation
Input Over-Voltage Protection: Bipolar Transient Voltage Suppressers (TVS), 5.6V clamp level typical
Resolution:
Millivolt input: 0.0025% (1 part in 40,000)
Thermocouple input: 0.1°C
Input Filter: Selectable digital filtering settings (none, low, medium, high)
Input Filter Bandwidth: Normal mode plus digital filtering within the ADC. Bandwidth (-3dB) varies with digital filter setting from 4Hz without filtering to 0.33Hz with high filtering.
Noise Rejection (Common Mode, High Filter): 155dB @ 60Hz, typical with 100 ohm input unbalance
Output
Output Range: 4 to 20mA DC
Output Compliance:
RLOAD = (VSUPPLY – 11V) / 0.020A.
RLOAD = 0 to 650 ohms @ 24V DC
Output Response Time (for step input change)
Time to reach 98% of output value (typical)
No filtering 104 milliseconds
Low filter 380 milliseconds
Medium filter 760 milliseconds
High filter 960 milliseconds
Environmental
Operating temperature: -40 to 80°C (-40° to 176°F)
Storage temperature: -40 to 85°C (-40 to 185°F)
Relative humidity: 5 to 95% non-condensing
Power Requirement: 12-32V DC SELV (Safety Extra Low Voltage), 24mA max
Isolation: 1500V AC peak. 250V AC (354V DC) continuous isolation between input and output circuits
Shock and Vibration Immunity:
Vibration: 4g, per IEC 60068-2-6
Shock: 25g, per IEC 60068-2-27
Electromagnetic Compatibility (EMC) Compliance:
Radiated Emissions: BS EN 61000-6-4, CISPR 16
RFI: BS EN 61000-6-2, IEC 61000-4-3
Conducted RFI: BS EN 61000-6-2, IEC 61000-4-6
ESD: BS EN 61000-6-2, IEC 61000-4-2
EFT: BS EN 61000-6-2, IEC 61000-4-4
Surge Immunity: BS EN 61000-6-2, IEC 61000-4-5
Approvals:
CE compliant. Designed for UL/cUL Class I Division 2 Groups ABCD, ATEX / IECEx Zone 2. II 3 G Ex nA IIC T4 Gc -40°C < Ta < +80°C
Physical
General: General-purpose enclosure designed for mounting on 35mm “T-type” DIN rail
Case Material: Self-extinguishing polyamide, UL94 V-0 rated, color light gray. General-purpose NEMA Type 1 enclosure
I/O Connectors: Removable plug-in terminal blocks rated for 12A/250V; AWG #26-12, stranded or solid copper wire
Dimensions: 12.5 x 114.5 x 99.0 mm (0.5 x 4.51 x 3.90 inches)
Shipping Weight: 0.22 kg (0.5 pounds) packed
- Easy setup and digital calibration via USB with Windows configuration software
- Easy setup and digital calibration via USB with Windows configuration software
- Universal thermocouple or millivolt input (TC Type J, K, T, R, S, E, B, N or ±100mV)
- Space-saving 12.5mm (0.5 inch) unit with pluggable terminals for convenient wiring
- High accuracy, linearity, stability, and reliability
- Low temperature drift (<80ppm/°C)
- User-selectable filtering (none, low, med., high)
- Supports sink or source output wiring
- Supports reverse-acting (inverse) output
- Selectable upscale or downscale operation for sensor errors and lead-break detection
- 1500V input isolation
- NAMUR-compliant output loop current
- Shock (50g) and vibration (5g) resistant
- Mounts on Type T DIN-rail
- Wide ambient operation (-40 to 80°C)
- CE compliant. UL/cUL Class I Div 2, ATEX / IECEx Zone 2 approvals
-
PS5R: Slim Line Power Supplies
- 10W, 15W, 30W, 60W, 90W, 120W, and 240W models
- Universal Input (85-264V AC / 100-370V DC)
- Lightweight and compact size
$95 – $245Select options -
TTC-SIP: Software
- Software Interface Package for Acromag DT, ST, TT Series Transmitters and SP, uBSP Series Signal Splitters.
- Includes configuration sofware CD-ROM (5040-xxx), isolator (USB-ISOLATOR) and two USB cable (4001-112, 4001-113) (Recommend one kit per customer.)
- Easy setup and digital calibration via USB with Windows configuration software.
- Download the configuration software only - from the Software Tab
$170Select options
Additional information
Weight | 8 oz |
---|---|
Dimensions | 4.51 × 0.5 × 3.9 in |
Part Number | TT233-0600: Transmitter |
Configuration | Agility Mobile App, Factory Calibration, USB Configuration, Windows Software Configuration |
Product Series | TT230 Series |
Power | Local Power, Loop Power |
-
Description
The TT233 model is a space-saving two-wire transmitter that isolates and converts a millivolt or thermocouple sensor input to a proportional 4-20mA control signal. Power is received from the output loop current or a DC supply when using a three-wire connection. The transmitter performs thermocouple linearization, cold junction compensation, and lead-break detection.
High-voltage isolation separates the input from the output circuit. Isolation protects from surges, reduces noise, and eliminates ground loop errors.
Setup and calibration are fast and easy with a convenient USB connection to your PC and Acromag’s Windows configuration software.
Advanced signal processing capabilities, variable range input, and convenient USB programming make this instrument a very versatile temperature measurement device. These transmitters can withstand harsh industrial environments and operate reliably across a wide temperature range with very low drift. They feature RFI, EMI, ESD, EFT, and surge protection plus low radiated emissions.
Performance Specifications
IMPORTANT: To prevent damage or errors from grounded PCs and surges, Acromag strongly recommends the use of their USB-ISOLATOR when configuring a TT230 Series transmitter.
USB Interface
USB Connector: USB Mini-B type socket, 5-pin
USB Data Rate: 12Mbps. USB v1.1 and 2.0 compatible
USB Transient Protection: Transient voltage suppression on power and data lines
USB Cable Length: 5.0 meters maximum
Driver: Not required. Uses built-in Human Interface Device (HID) USB drivers of the Windows operating systemInput
Default Configuration/Calibration:
Input: TC J, -210 to 760°C, high filter, Break: up
Output: 4 to 20mAInput Ranges and Accuracy
Input Range Accuracy
TC J -210 to 760°C (-346 to 1400°F) ±0.5°C
TC K -200 to 1372°C (-328 to 2502°F) ±0.5°C
TC T -260 to 400°C (-436 to 752°F) ±0.5°C
TC R -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC S -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC E -200 to 1000°C (-328 to 1832°F) ±0.5°C
TC B 260 to 1820°C (500 to 3308°F) ±1.0°C
TC N -230 to -1300°C (-274 to 2372°F ±1.0°C
mV -100 to 100mV ±0.1mVThermocouple Reference (Cold Junction Compensation): ±0.2°C typical, ±0.5°C maximum at 25°C
Ambient Temperature Effect: Better than ±80ppm/°C (±0.008%/°C)
Zero Scaling Adjust: 0 to 95% of range, typical
Lead Break (Sensor Burnout) Detection: Configurable for either upscale (24mA) or downscale (3.3mA) operation
Input Over-Voltage Protection: Bipolar Transient Voltage Suppressers (TVS), 5.6V clamp level typical
Resolution:
Millivolt input: 0.0025% (1 part in 40,000)
Thermocouple input: 0.1°C
Input Filter: Selectable digital filtering settings (none, low, medium, high)
Input Filter Bandwidth: Normal mode plus digital filtering within the ADC. Bandwidth (-3dB) varies with digital filter setting from 4Hz without filtering to 0.33Hz with high filtering.
Noise Rejection (Common Mode, High Filter): 155dB @ 60Hz, typical with 100 ohm input unbalanceOutput
Output Range: 4 to 20mA DC
Output Compliance:
RLOAD = (VSUPPLY – 11V) / 0.020A.
RLOAD = 0 to 650 ohms @ 24V DCOutput Response Time (for step input change)
Time to reach 98% of output value (typical)
No filtering 104 milliseconds
Low filter 380 milliseconds
Medium filter 760 milliseconds
High filter 960 millisecondsEnvironmental
Operating temperature: -40 to 80°C (-40° to 176°F)
Storage temperature: -40 to 85°C (-40 to 185°F)
Relative humidity: 5 to 95% non-condensing
Power Requirement: 12-32V DC SELV (Safety Extra Low Voltage), 24mA max
Isolation: 1500V AC peak. 250V AC (354V DC) continuous isolation between input and output circuits
Shock and Vibration Immunity:
Vibration: 4g, per IEC 60068-2-6
Shock: 25g, per IEC 60068-2-27
Electromagnetic Compatibility (EMC) Compliance:
Radiated Emissions: BS EN 61000-6-4, CISPR 16
RFI: BS EN 61000-6-2, IEC 61000-4-3
Conducted RFI: BS EN 61000-6-2, IEC 61000-4-6
ESD: BS EN 61000-6-2, IEC 61000-4-2
EFT: BS EN 61000-6-2, IEC 61000-4-4
Surge Immunity: BS EN 61000-6-2, IEC 61000-4-5
Approvals:
CE compliant. Designed for UL/cUL Class I Division 2 Groups ABCD, ATEX / IECEx Zone 2. II 3 G Ex nA IIC T4 Gc -40°C < Ta < +80°CPhysical
General: General-purpose enclosure designed for mounting on 35mm “T-type” DIN rail
Case Material: Self-extinguishing polyamide, UL94 V-0 rated, color light gray. General-purpose NEMA Type 1 enclosure
I/O Connectors: Removable plug-in terminal blocks rated for 12A/250V; AWG #26-12, stranded or solid copper wire
Dimensions: 12.5 x 114.5 x 99.0 mm (0.5 x 4.51 x 3.90 inches)
Shipping Weight: 0.22 kg (0.5 pounds) packed -
Features & Benefits
- Easy setup and digital calibration via USB with Windows configuration software
- Easy setup and digital calibration via USB with Windows configuration software
- Universal thermocouple or millivolt input (TC Type J, K, T, R, S, E, B, N or ±100mV)
- Space-saving 12.5mm (0.5 inch) unit with pluggable terminals for convenient wiring
- High accuracy, linearity, stability, and reliability
- Low temperature drift (<80ppm/°C)
- User-selectable filtering (none, low, med., high)
- Supports sink or source output wiring
- Supports reverse-acting (inverse) output
- Selectable upscale or downscale operation for sensor errors and lead-break detection
- 1500V input isolation
- NAMUR-compliant output loop current
- Shock (50g) and vibration (5g) resistant
- Mounts on Type T DIN-rail
- Wide ambient operation (-40 to 80°C)
- CE compliant. UL/cUL Class I Div 2, ATEX / IECEx Zone 2 approvals
-
Tech Papers
Minimizing Measurement Errors When Making Thermocouple to Transmitter Connections White Paper (Log in to view the file)How To Prevent Temperature Measurement Errors It will give you a keen understanding of the three basic laws of thermocouples: Homogeneous materials, Intermediate Metals, and Successive/Intermediate Temperatures. It is helpful in weeding out potential sources of error in a thermocouple measurement system.Temperature Measurement Using Thermocouples White Paper (Log in to view the file)The Basics of Temperature Measurement Using Thermocouples Choosing a temperature sensor for an application is not as simple as picking a thermocouple type with a compatible temperature range. You must give consideration to the sensor material type, the application temperature range, the relative sensitivity of the sensor, the limitations of its insulation material, and its...How to use Thermocouple Transmitters to Monitor Temperatures in Paint Systems Application NoteThis document illustrates using Acromag’s TT330 Series to monitor high temperatures in an automotive paint curing oven and transmit to the existing PLC 4-20mA input card/software setup. Defining the Problem The area around an auto manufacturer’s paint curing ovens is at elevated temperatures affecting the performance of locally installed instrumentation. Placing Signal Conditioners rated for... -
Specs & Data Sheets
-
Software
-
Accessories
-
PS5R: Slim Line Power Supplies
- 10W, 15W, 30W, 60W, 90W, 120W, and 240W models
- Universal Input (85-264V AC / 100-370V DC)
- Lightweight and compact size
$95 – $245Select options -
TTC-SIP: Software
- Software Interface Package for Acromag DT, ST, TT Series Transmitters and SP, uBSP Series Signal Splitters.
- Includes configuration sofware CD-ROM (5040-xxx), isolator (USB-ISOLATOR) and two USB cable (4001-112, 4001-113) (Recommend one kit per customer.)
- Easy setup and digital calibration via USB with Windows configuration software.
- Download the configuration software only - from the Software Tab
$170Select options
-
Additional information
Additional information
Weight 8 oz Dimensions 4.51 × 0.5 × 3.9 in Part Number TT233-0600: Transmitter
Configuration Agility Mobile App, Factory Calibration, USB Configuration, Windows Software Configuration
Product Series TT230 Series
Power Local Power, Loop Power
Please login to submit this form.