DT333: Thermocouple / milliVolt Input Four-Wire Dual Transmitter
Product short description:
- Dual channels
- Universal thermocouple, mV inputs
- Isolated current or voltage outputs
- 6-32V DC local/bus power
The DT333 model is a four-wire dual transmitter that isolates and converts millivolt or thermocouple sensor inputs to proportional control signals. Each channel supports DC current or voltage output.
Click here to watch a short video highlighting the features of the DT333.
- Description
- Features & Benefits
- Tech Papers
- Specs & Data Sheets
- Software
- Accessories
- Additional information
DT330 series signal conditioners provide two independent I/O channels in a single, space-saving unit. The DT333 model is a four-wire dual transmitter that isolates and converts millivolt or thermocouple sensor inputs to proportional control signals. Each channel supports DC current or voltage output. An optional DIN rail bus can deliver primary or redundant power to multiple units.
High-voltage isolation separates inputs, outputs, and power from each other. Isolation protects from surges, reduces noise, and eliminates ground loop errors.
Setup and calibration are fast and easy with a convenient USB connection to your PC and Acromag’s Windows configuration software. The Android app enables setup with mobile devices.
Advanced signal processing capabilities, variable range input/output, and convenient USB programming make this instrument very versatile. These transmitters can withstand harsh industrial environments and operate reliably across a wide temperature range with very low drift. They feature RFI, EMI, ESD, EFT, and surge protection plus low radiated emissions.
Performance Specifications
IMPORTANT: To prevent damage or errors from grounded PCs and surges, Acromag strongly recommends use of a USB isolator like Acromag’s USB-Isolator when configuring a DT330 Series transmitter.
USB Interface
USB Connection
Type: USB Mini-B type socket, 5-pin
Data Rate: 12Mbps. USB v1.1 and 2.0 compatible
Maximum cable length: 5.0 meters
Transient voltage suppression on power and data lines.
USB Driver:
Not required. Uses built-in Human Interface Device (HID) USB drivers of the Windows operating system.
Input (two channels)
Default Configuration/Calibration
Input: TC J, -210 to 760°C, medium filter
Output: 4 to 20mA, upscale break detect
Input Ranges
Input Range Accuracy
TC J -210 to 760°C (-346 to 1400°F) ±0.5°C
TC K -200 to 1372°C (-328 to 2502°F) ±0.5°C
TC T -260 to 400°C (-436 to 752°F) ±0.5°C
TC R -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC S -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC E -200 to 1000°C (-328 to 1832°F) ±0.5°C
TC B 260 to 1820°C (500 to 3308°F) ±1.0°C
TC N -230 to -170°C (-382 to -274°F) ±1.0°C
TC N -230 to -1300°C (-274 to 2372°F ±0.5°C
mV -100 to 100mV ±0.05%
Thermocouple Reference (Cold Junction Compensation): ±0.2°C typical, ±0.5°C maximum at 25°C.
Ambient Temperature Effect: Better than ±80ppm/°C (±0.008%/°C).
Scaling Adjust: Full range.
Lead Break (Sensor Burnout) Detection: Upscale/downscale full range.
Input Impedance: 15M ohms.
Input Over-Voltage Protection: Bipolar Transient Voltage Suppression (TVS) and diode clamping.
Input Filter: RC filter plus variable digital filter (none, low, medium, high).
Noise Rejection
Common Mode: 96dB no filter (134dB high filter).
Normal Mode: 0.12dB no filter, 60Hz (>80dB med/high filter).
Output (two channels)
D/A Converters (DAC): Two 16-bit D/A converters.
Output Ranges
±10V (±11V maximum).
±5V (±5.5V maximum).
0 to 10V (11V maximum).
0 to 5V (5.5V maximum).
0 to 20mA (24mA maximum).
4 to 20mA (24mA maximum).
Output Accuracy: ±0.05%, typical. ±0.1%, maximum.
Output Load
Voltage output: 1K ohms minimum.
Current output: 0-550 ohms.
Output Compliance: 11V, typical.
Output Response Time (for step input change)
Time to reach 98% of output value (typical)
No filtering 13 milliseconds
Low filter 38 milliseconds
Medium filter 122 milliseconds
High filter 1158 milliseconds
Output Ripple: Less than ±0.1% of output span.
Environmental
Operating Temperature
Operation: -40 to 70°C (-40° to 158°F)
Storage: -40 to 85°C (-40 to 185°F)
Relative humidity: 5 to 95% non-condensing
Power Requirement: 6-32V DC SELV, 1.6W max.
Isolation: 1500V AC peak. 250V AC (354V DC) continuous isolation between inputs, outputs, and power (5-way).
Shock and Vibration Immunity
Vibration: 4g, per IEC 60068-2-6
Shock: 25g, per IEC 60068-2-27
Approvals
CE compliant. Designed for UL/cUL Class I Division 2 Groups ABCD, ATEX / IECEx Zone 2. II 3 G Ex nA IIC T4 Gc -40°C < Ta < +80°C
Electromagnetic Compatibility (EMC) Compliance
Radiated Emissions: BS EN 61000-6-4, CISPR 16
RFI: BS EN 61000-6-2, IEC 61000-4-3
Conducted RFI: BS EN 61000-6-2, IEC 61000-4-6
ESD: BS EN 61000-6-2, IEC 61000-4-2
EFT: BS EN 61000-6-2, IEC 61000-4-4
Surge Immunity: BS EN 61000-6-2, IEC 61000-4-5
Physical
General: General-purpose enclosure designed for mounting on 35mm “T-type” DIN rail.
Case Material: Self-extinguishing polyamide, UL94 V-0 rated.
I/O Connectors: Removable plug-in terminal blocks rated for 12A/250V; AWG #26-12, stranded or solid copper wire.
Dimensions: 17.5 x 114.5 x 99.0 mm (0.7 x 4.51 x 3.90 inches).
Unit weight: 0.16 kg (0.35 pounds).
Shipping Weight: 0.22 kg (0.5 pounds) packed.
- Operate as a dual transmitter, a single transmitter, or a signal splitter
- Easy configuration via USB with Windows software or Agility™ app for Android
- Independently adjustable and scalable input and output ranges
- Selectable thermocouple/millivolt input types: (TC Type J, K, T, R, S, E, B, N, ±100mV, ±1V)
- Selectable current and voltage output ranges: 0-20mA, 4-20mA, ±5V, ±10V, 0-5V, 0-10V DC
- Supports reverse-acting (inverse) output
- High accuracy, linearity, stability, and reliability
- User-selectable filtering (none, low, med., high)
- Selectable up/downscale fault detection
- Bus power, local power, or both (redundancy)
- Space-saving 17.5mm (0.7 inch) unit with pluggable terminals for convenient wiring
- 1500V input isolation, 5-way, (power/input/output)
- Wide ambient operation (-40 to 70°C)
- Approvals: CE compliant. UL/cUL Class I Div 2, ATEX/IECEx Zone 2
-
TTBus-Kit: DIN Rail Bus Power Connector
- One kit supports multiple SP Series Splitters or DT and TT Series transmitters.
$30Select options -
TTC-SIP: Software
- Software Interface Package for Acromag DT, ST, TT Series Transmitters and SP, uBSP Series Signal Splitters.
- Includes configuration sofware CD-ROM (5040-xxx), isolator (USB-ISOLATOR) and two USB cable (4001-112, 4001-113) (Recommend one kit per customer.)
- Easy setup and digital calibration via USB with Windows configuration software.
- Download the configuration software only - from the Software Tab
$170Select options -
USB Isolator
- USB-powered, USB 2.0 and 1.1 compatible
- 1500V AC / 2100V DC isolation
- No drivers required
$110Select options
Additional information
Weight | 16 oz |
---|---|
Dimensions | 13 × 12 × 3 in |
Part Number | DT333-0700: transmitter |
Configuration | Agility Mobile App, Factory Calibration, Windows Software Configuration |
Product Series | DT330 Series |
-
Description
DT330 series signal conditioners provide two independent I/O channels in a single, space-saving unit. The DT333 model is a four-wire dual transmitter that isolates and converts millivolt or thermocouple sensor inputs to proportional control signals. Each channel supports DC current or voltage output. An optional DIN rail bus can deliver primary or redundant power to multiple units.
High-voltage isolation separates inputs, outputs, and power from each other. Isolation protects from surges, reduces noise, and eliminates ground loop errors.
Setup and calibration are fast and easy with a convenient USB connection to your PC and Acromag’s Windows configuration software. The Android app enables setup with mobile devices.
Advanced signal processing capabilities, variable range input/output, and convenient USB programming make this instrument very versatile. These transmitters can withstand harsh industrial environments and operate reliably across a wide temperature range with very low drift. They feature RFI, EMI, ESD, EFT, and surge protection plus low radiated emissions.
Performance Specifications
IMPORTANT: To prevent damage or errors from grounded PCs and surges, Acromag strongly recommends use of a USB isolator like Acromag’s USB-Isolator when configuring a DT330 Series transmitter.
USB Interface
USB Connection
Type: USB Mini-B type socket, 5-pin
Data Rate: 12Mbps. USB v1.1 and 2.0 compatible
Maximum cable length: 5.0 meters
Transient voltage suppression on power and data lines.
USB Driver:
Not required. Uses built-in Human Interface Device (HID) USB drivers of the Windows operating system.Input (two channels)
Default Configuration/Calibration
Input: TC J, -210 to 760°C, medium filter
Output: 4 to 20mA, upscale break detectInput Ranges
Input Range Accuracy
TC J -210 to 760°C (-346 to 1400°F) ±0.5°C
TC K -200 to 1372°C (-328 to 2502°F) ±0.5°C
TC T -260 to 400°C (-436 to 752°F) ±0.5°C
TC R -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC S -50 to 1768°C (-58 to 3214°F) ±1.0°C
TC E -200 to 1000°C (-328 to 1832°F) ±0.5°C
TC B 260 to 1820°C (500 to 3308°F) ±1.0°C
TC N -230 to -170°C (-382 to -274°F) ±1.0°C
TC N -230 to -1300°C (-274 to 2372°F ±0.5°C
mV -100 to 100mV ±0.05%Thermocouple Reference (Cold Junction Compensation): ±0.2°C typical, ±0.5°C maximum at 25°C.
Ambient Temperature Effect: Better than ±80ppm/°C (±0.008%/°C).
Scaling Adjust: Full range.
Lead Break (Sensor Burnout) Detection: Upscale/downscale full range.
Input Impedance: 15M ohms.
Input Over-Voltage Protection: Bipolar Transient Voltage Suppression (TVS) and diode clamping.
Input Filter: RC filter plus variable digital filter (none, low, medium, high).
Noise Rejection
Common Mode: 96dB no filter (134dB high filter).
Normal Mode: 0.12dB no filter, 60Hz (>80dB med/high filter).Output (two channels)
D/A Converters (DAC): Two 16-bit D/A converters.
Output Ranges
±10V (±11V maximum).
±5V (±5.5V maximum).
0 to 10V (11V maximum).
0 to 5V (5.5V maximum).
0 to 20mA (24mA maximum).
4 to 20mA (24mA maximum).Output Accuracy: ±0.05%, typical. ±0.1%, maximum.
Output Load
Voltage output: 1K ohms minimum.
Current output: 0-550 ohms.Output Compliance: 11V, typical.
Output Response Time (for step input change)
Time to reach 98% of output value (typical)
No filtering 13 milliseconds
Low filter 38 milliseconds
Medium filter 122 milliseconds
High filter 1158 milliseconds
Output Ripple: Less than ±0.1% of output span.
Environmental
Operating Temperature
Operation: -40 to 70°C (-40° to 158°F)
Storage: -40 to 85°C (-40 to 185°F)
Relative humidity: 5 to 95% non-condensingPower Requirement: 6-32V DC SELV, 1.6W max.
Isolation: 1500V AC peak. 250V AC (354V DC) continuous isolation between inputs, outputs, and power (5-way).
Shock and Vibration Immunity
Vibration: 4g, per IEC 60068-2-6
Shock: 25g, per IEC 60068-2-27Approvals
CE compliant. Designed for UL/cUL Class I Division 2 Groups ABCD, ATEX / IECEx Zone 2. II 3 G Ex nA IIC T4 Gc -40°C < Ta < +80°CElectromagnetic Compatibility (EMC) Compliance
Radiated Emissions: BS EN 61000-6-4, CISPR 16RFI: BS EN 61000-6-2, IEC 61000-4-3
Conducted RFI: BS EN 61000-6-2, IEC 61000-4-6
ESD: BS EN 61000-6-2, IEC 61000-4-2
EFT: BS EN 61000-6-2, IEC 61000-4-4
Surge Immunity: BS EN 61000-6-2, IEC 61000-4-5
Physical
General: General-purpose enclosure designed for mounting on 35mm “T-type” DIN rail.
Case Material: Self-extinguishing polyamide, UL94 V-0 rated.
I/O Connectors: Removable plug-in terminal blocks rated for 12A/250V; AWG #26-12, stranded or solid copper wire.
Dimensions: 17.5 x 114.5 x 99.0 mm (0.7 x 4.51 x 3.90 inches).
Unit weight: 0.16 kg (0.35 pounds).
Shipping Weight: 0.22 kg (0.5 pounds) packed.
-
Features & Benefits
- Operate as a dual transmitter, a single transmitter, or a signal splitter
- Easy configuration via USB with Windows software or Agility™ app for Android
- Independently adjustable and scalable input and output ranges
- Selectable thermocouple/millivolt input types: (TC Type J, K, T, R, S, E, B, N, ±100mV, ±1V)
- Selectable current and voltage output ranges: 0-20mA, 4-20mA, ±5V, ±10V, 0-5V, 0-10V DC
- Supports reverse-acting (inverse) output
- High accuracy, linearity, stability, and reliability
- User-selectable filtering (none, low, med., high)
- Selectable up/downscale fault detection
- Bus power, local power, or both (redundancy)
- Space-saving 17.5mm (0.7 inch) unit with pluggable terminals for convenient wiring
- 1500V input isolation, 5-way, (power/input/output)
- Wide ambient operation (-40 to 70°C)
- Approvals: CE compliant. UL/cUL Class I Div 2, ATEX/IECEx Zone 2
-
Tech Papers
Minimizing Measurement Errors When Making Thermocouple to Transmitter Connections White Paper (Log in to view the file)How To Prevent Temperature Measurement Errors It will give you a keen understanding of the three basic laws of thermocouples: Homogeneous materials, Intermediate Metals, and Successive/Intermediate Temperatures. It is helpful in weeding out potential sources of error in a thermocouple measurement system.Temperature Measurement Using Thermocouples White Paper (Log in to view the file)The Basics of Temperature Measurement Using Thermocouples Choosing a temperature sensor for an application is not as simple as picking a thermocouple type with a compatible temperature range. You must give consideration to the sensor material type, the application temperature range, the relative sensitivity of the sensor, the limitations of its insulation material, and its...How to use Thermocouple Transmitters to Monitor Temperatures in Paint Systems Application NoteThis document illustrates using Acromag’s TT330 Series to monitor high temperatures in an automotive paint curing oven and transmit to the existing PLC 4-20mA input card/software setup. Defining the Problem The area around an auto manufacturer’s paint curing ovens is at elevated temperatures affecting the performance of locally installed instrumentation. Placing Signal Conditioners rated for... -
Specs & Data Sheets
-
Software
-
Accessories
-
TTBus-Kit: DIN Rail Bus Power Connector
- One kit supports multiple SP Series Splitters or DT and TT Series transmitters.
$30Select options -
TTC-SIP: Software
- Software Interface Package for Acromag DT, ST, TT Series Transmitters and SP, uBSP Series Signal Splitters.
- Includes configuration sofware CD-ROM (5040-xxx), isolator (USB-ISOLATOR) and two USB cable (4001-112, 4001-113) (Recommend one kit per customer.)
- Easy setup and digital calibration via USB with Windows configuration software.
- Download the configuration software only - from the Software Tab
$170Select options -
USB Isolator
- USB-powered, USB 2.0 and 1.1 compatible
- 1500V AC / 2100V DC isolation
- No drivers required
$110Select options
-
Additional information
Additional information
Weight 16 oz Dimensions 13 × 12 × 3 in Part Number DT333-0700: transmitter
Configuration Agility Mobile App, Factory Calibration, Windows Software Configuration
Product Series DT330 Series