These models convert sensor inputs to proportional process current or voltage output signals.

Models

250T: Loop-powered transmitter series
350T: DC-powered transmitter series
450T: AC-powered transmitter series

Performance Specifications

Input Ranges:
milliVolt: -25 to 250mV
Narrow Span: 3 to 5mV, custom calibration
Output Ranges:
DC Current: 4 to 20mA
DC voltage: 0 to 5V or 0 to 10V
Power Requirements:
250T: 12 to 50V DC @ 20mA (loop-powered)

350T: DC Voltage Source
Output Range                Power
4 to 20mA               10 to 36V DC @ 30mA
0 to 5V                      10 to 36V DC @ 9mA
0 to 10V                12.5 to 36V DC @ 9mA

450T: 115V or 230V AC, ±10%, 50 to 60Hz
Output Range                 Power
4 to 20mA                  115V AC @ 0.050A
4 to 20mA                  230V AC @ 0.025A
0 to 5V, 0 to 10V       115V AC @ 0.020A
0 to 5V, 0 to 10V      230V AC @ 0.010A

Ambient Temperature Range:
Operating: -13 to 185°F (-25 to 85°C)
Storage: -40 to 185°F (-40 to 85°C)
Accuracy:
±0.1% of calibrated span or ±0.01mV, whichever is greater. Includes repeat-ability, hysteresis, terminal point linearity, and adjustment resolution.
Ambient Temperature Effect:
Less than ±0.01% of output span per °F (±0.018% per °C).
±0.025% of output span per °F (±0.045% per °C) for narrow span units.
(Specification includes the combined effects of zero and span over temperature)
Noise Resistance:
RFI: Less than ±0.5% ,of output span effect.
EMI: Less than ±0.25% of output span effect.
Noise Rejection:
Common Mode: 130dB at 60Hz, 100 ohm unbalance
Normal Mode: 30dB at 60Hz, 100 ohm source
Response Time: Output reaches 98% of output span in 300mS.
Bandwidth: -3dB at 3 Hz, typical
Output Compliance:
250T: RLOAD (max.) = (VSUPPLY – 12V) / 20mA
350T: RLOAD (max.) = (VSUPPLY – 2.5V) / 20mA
450T: RLOAD = 600 ohms

  • Excellent accuracy and stability ensure reliable measurements in harsh industrial environments
  • RFI and EMI resistance minimize the effects of environmental noise
  • 90% span adjustment enables precise application calibration
  • 1500V AC peak isolation (250V AC or 354V DC continuous) prevents ground loops
  • Compact, 1-inch wide housing uses less space for easier installation in control panels
  • Low power consumption. 350T units operate on currents as low as 9mA to help prevent expensive upgrades to larger power supplies

Manuals

250T-mV Series User Manual (Log in to download the file)

350T-mV Series User Manual (Log in to download the file)

450T-mV Series User Manual (Log in to download the file)

Additional information

Weight 16 oz
Dimensions 3 × 1 × 3.2 in
Part Number

250T-MV1-DIN-NCR: up to 80mV input, DIN rail G or T mount, no certification/approval required, 250T-MV2-DIN-NCR: up to 375mV input, DIN rail G or T mount, no certification/approval required, 250T-MV3-DIN-NCR-C: narrow span, up to 30mV input, DIN rail G or T mount, no certification/approval required Unit requires factory calibration, specify ranges on order, 350T-MV1-V0-DIN-NCR: up to 80mV input; 0 to 10V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV1-V5-DIN-NCR: up to 80mV input; 0 to 5V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV1-Y-DIN-NCR: up to 80mV input; 4 to 20mA DC output; DIN rail G or T mount; no certification/approval required, 350T-MV2-V0-DIN-NCR: up to 375mV input; 0 to 10V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV2-V5-DIN-NCR: up to 375mV output; 0 to 5V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV2-Y-DIN-NCR: up to 375mV output; 4 to 20mA DC output; DIN rail G or T mount; no certification/approval required, 350T-MV3-Y-DIN-NCR-C: narrow span, up to 30mV input, 4 to 20mA DC output; DIN rail G or T mount; no certification/approval required Unit requires factory calibration, specify ranges on order, 450T-MV1-Y-1-DIN-NCR: up to 80mV input; 4 to 20mA DC output, 115V AC power; DIN rail G or T mount; no certification/approval required, 450T-MV2-Y-1-DIN-NCR: up to 375mV input; 4-20mA DC output; 115V AC power; DIN rail G or T mount; no certification/approval required, 450T-MV3-Y-1-DIN-NCR-C: narrow span, up to 30mV input; 4 to 20mA DC output; 115V AC power; DIN rail G or T mount; no certification/approval required Unit requires factory calibration, specify ranges on order

Product Series

FlatPack Series

  • Description

    These models convert sensor inputs to proportional process current or voltage output signals.

    Models

    250T: Loop-powered transmitter series
    350T: DC-powered transmitter series
    450T: AC-powered transmitter series

    Performance Specifications

    Input Ranges:
    milliVolt: -25 to 250mV
    Narrow Span: 3 to 5mV, custom calibration
    Output Ranges:
    DC Current: 4 to 20mA
    DC voltage: 0 to 5V or 0 to 10V
    Power Requirements:
    250T: 12 to 50V DC @ 20mA (loop-powered)

    350T: DC Voltage Source
    Output Range                Power
    4 to 20mA               10 to 36V DC @ 30mA
    0 to 5V                      10 to 36V DC @ 9mA
    0 to 10V                12.5 to 36V DC @ 9mA

    450T: 115V or 230V AC, ±10%, 50 to 60Hz
    Output Range                 Power
    4 to 20mA                  115V AC @ 0.050A
    4 to 20mA                  230V AC @ 0.025A
    0 to 5V, 0 to 10V       115V AC @ 0.020A
    0 to 5V, 0 to 10V      230V AC @ 0.010A

    Ambient Temperature Range:
    Operating: -13 to 185°F (-25 to 85°C)
    Storage: -40 to 185°F (-40 to 85°C)
    Accuracy:
    ±0.1% of calibrated span or ±0.01mV, whichever is greater. Includes repeat-ability, hysteresis, terminal point linearity, and adjustment resolution.
    Ambient Temperature Effect:
    Less than ±0.01% of output span per °F (±0.018% per °C).
    ±0.025% of output span per °F (±0.045% per °C) for narrow span units.
    (Specification includes the combined effects of zero and span over temperature)
    Noise Resistance:
    RFI: Less than ±0.5% ,of output span effect.
    EMI: Less than ±0.25% of output span effect.
    Noise Rejection:
    Common Mode: 130dB at 60Hz, 100 ohm unbalance
    Normal Mode: 30dB at 60Hz, 100 ohm source
    Response Time: Output reaches 98% of output span in 300mS.
    Bandwidth: -3dB at 3 Hz, typical
    Output Compliance:
    250T: RLOAD (max.) = (VSUPPLY – 12V) / 20mA
    350T: RLOAD (max.) = (VSUPPLY – 2.5V) / 20mA
    450T: RLOAD = 600 ohms

  • Features & Benefits

    • Excellent accuracy and stability ensure reliable measurements in harsh industrial environments
    • RFI and EMI resistance minimize the effects of environmental noise
    • 90% span adjustment enables precise application calibration
    • 1500V AC peak isolation (250V AC or 354V DC continuous) prevents ground loops
    • Compact, 1-inch wide housing uses less space for easier installation in control panels
    • Low power consumption. 350T units operate on currents as low as 9mA to help prevent expensive upgrades to larger power supplies
  • Specs & Data Sheets

    Manuals

    250T-mV Series User Manual (Log in to download the file)

    350T-mV Series User Manual (Log in to download the file)

    450T-mV Series User Manual (Log in to download the file)

  • Accessories

  • Additional information

    Additional information

    Weight 16 oz
    Dimensions 3 × 1 × 3.2 in
    Part Number

    250T-MV1-DIN-NCR: up to 80mV input, DIN rail G or T mount, no certification/approval required, 250T-MV2-DIN-NCR: up to 375mV input, DIN rail G or T mount, no certification/approval required, 250T-MV3-DIN-NCR-C: narrow span, up to 30mV input, DIN rail G or T mount, no certification/approval required Unit requires factory calibration, specify ranges on order, 350T-MV1-V0-DIN-NCR: up to 80mV input; 0 to 10V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV1-V5-DIN-NCR: up to 80mV input; 0 to 5V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV1-Y-DIN-NCR: up to 80mV input; 4 to 20mA DC output; DIN rail G or T mount; no certification/approval required, 350T-MV2-V0-DIN-NCR: up to 375mV input; 0 to 10V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV2-V5-DIN-NCR: up to 375mV output; 0 to 5V DC output; DIN rail G or T mount; no certification/approval required, 350T-MV2-Y-DIN-NCR: up to 375mV output; 4 to 20mA DC output; DIN rail G or T mount; no certification/approval required, 350T-MV3-Y-DIN-NCR-C: narrow span, up to 30mV input, 4 to 20mA DC output; DIN rail G or T mount; no certification/approval required Unit requires factory calibration, specify ranges on order, 450T-MV1-Y-1-DIN-NCR: up to 80mV input; 4 to 20mA DC output, 115V AC power; DIN rail G or T mount; no certification/approval required, 450T-MV2-Y-1-DIN-NCR: up to 375mV input; 4-20mA DC output; 115V AC power; DIN rail G or T mount; no certification/approval required, 450T-MV3-Y-1-DIN-NCR-C: narrow span, up to 30mV input; 4 to 20mA DC output; 115V AC power; DIN rail G or T mount; no certification/approval required Unit requires factory calibration, specify ranges on order

    Product Series

    FlatPack Series