XT1230: 16-Channel Single-Ended Analog Current Input Module
Please sign in or register to see model options and to add products to your cart.
Product short description:
- 0-11mA, 0-20mA, 4-20mA, ±20mA, or 0-20 amps AC Input
- 16 analog single-ended current input channels
- 12 to 32V DC Power (2.8W)
- Modbus TCP/IP, Ethernet/IP, Profinet
- i2o® peer-to-peer available for Modbus TCP/IP only
The XT1230 offers an isolated Ethernet network interface for up to to sixteen single-ended current input channels.
- Description
- Features & Benefits
- Tech Papers
- Specs & Data Sheets
- Software
- Accessories
- Additional information
The XT1230 offers an isolated Ethernet network interface for up to to sixteen single-ended current input channels. Single-ended inputs enable a higher channel density to save space and a lower cost per channel.
Rugged construction, high density design, and easy USB-to-PC/Windows setup combine for a very effective and reliable module. These units are ideal for remote monitoring, distributed control, or SCADA applications.
Input Ranges:
DC Current:
0 to 11mA, 0 to 20mA, 4 to 20mA, ±20mA
0 to 20 amps AC (with optional AC sensor)
Ethernet Communication:
Modbus TCP/IP, i2o® peer-to-peer available for Modbus TCP/IP only
Ethernet/IP
Profinet
10/100Base-T(X)
PriorityChannel™ device determinism
Power Requirement: 12 to 32V DC (2.8W)
Performance Specifications
IMPORTANT: To prevent damage or errors from grounded PCs and surges, Acromag strongly recommends use of the USB-ISOLATOR when configuring an XT1000 I/O module.
USB Interface
USB Connector:
Type: USB Mini-B type socket, 5-pin
Data Rate: 12Mbps. USB v1.1 and 2.0 compatible
Cable Length: 5.0 meters maximum
USB Transient Protection: Transient voltage suppression on power and data lines
Driver: Not required. Uses Windows (HID) drivers
Input
Accuracy: ±0.05% of span, typical for nominal input ranges
Analog to Digital Converter (A/D): 16-bit Σ-Δ converter. 1.476uA/bit resolution
Noise Rejection: Better than -110dB @ 60Hz
Input Filter Bandwidth: -3dB at 25KHz, typical
Input Conversion Rate: 10ms for all 16 input channels
Input Impedance: 27.4 ohms
Ethernet Communication
Protocols:
Modbus TCP/IP, i2o® peer-to-peer available for Modbus TCP/IP only
Ethernet/IP
or Profinet, depending on model number
Ethernet Communication Controller: Innovasic RapID™ Platform with PriorityChannel™ for determinism at the device regardless of network load
Modbus TCP/IP (slave): Port 502 reserved. Supports up to 10 sockets
i2o Peer-to-Peer (master/slave): Can map each of 16 analog input channels separately to output channels. Timed (1-65535 sec) or percent of change updates. Supports GPRS/GSM systems.
Ethernet/IP (adapter): Supports 10 connections. EDS file on website
Profinet (server): Supports 1 connection. GSDML file on website
Connectors: Two shielded 8-pin RJ-45 sockets, 10BaseT/100BaseTX
Wiring: Auto-crossover for MDI or MDI-X
IP Address: User-configurable. 192.168.1.100 default IP address
Data Rate: Auto-negotiated, 10Mbps or 100Mbps
Compliance: IEEE 802.3, 802.3u, 802.3x
Environmental
Operating temperature: -40 to 70°C (-40 to 158°F)
Storage temperature: -40 to 85°C (-40 to 185°F)
Relative humidity: 5 to 95% non-condensing
MTBF:
463,547 hrs. at 25°C
345,200 hrs. at 40°C
Power Requirement: 12 to 32V DC, 2.8W maximum (113mA maximum @ 24V)
Isolation:
4-way isolation between I/O channels, network (each port), and power
Peak: 1500V AC, ANSI/ISA-82.01-1988
Continuous: 250V AC, 354V DC
Shock and Vibration Immunity:
Vibration: 4g, per IEC 60068-2-64
Shock: 25g, per IEC 60068-2-27
Electromagnetic Compatibility (EMC) Compliance:
Radiated Emissions: BS EN 61000-6-4, CISPR 16
RFI: BS EN 61000-6-2, IEC 61000-4-3
Conducted RFI: BS EN 61000-6-2, IEC 61000-4-6
ESD: BS EN 61000-6-2, IEC 61000-4-2
EFT: BS EN 61000-6-2, IEC 61000-4-4
Surge Immunity: BS EN 61000-6-2, IEC 61000-4-5
Approvals:
CE compliant. UL/cUL Class I; Div. 2 Zone 2. ATEX Cert. II 3 G Ex nA IIC T4 Gc -40°C < Ta < +80°C
Physical
General: General purpose plastic enclosure for mounting on 35mm “T-type” DIN rail
Case Material: Self-extinguishing polyamide, UL94 V-0 rated, color light gray. General purpose NEMA Type 1 enclosure
Circuit Board: Military grade fire-retardant epoxy glass (IPC-4101/98)
I/O Connectors: Removable plug-in type terminal blocks rated for 12A/250V; AWG #26-12, stranded/solid copper wire
Dimensions:
Width = 22.5mm (0.9 inches)
Length = 114.5mm (4.51 inches)
Depth = 99.0mm (3.90 inches)
Shipping Weight: 0.5 pounds (0.22 Kg) packed
- i2o® peer-to-peer available for Modbus TCP/IP only
- i2o® peer-to-peer updates based on change-of-state and/or timed updates
- Easy setup with Windows software via USB
- Low input impendance (27 ohms) reduces loading on current loops
- User-configurable sample averaging (1-200) on a per-channel basis
- 10ms network updates for all 16 input channels
- High-resolution 16-bit Σ∆ A/D converter ensures precise, high accuracy measurements
- High-Density 22.5mm wide package with pluggable, front-facing terminals
- Dual Ethernet 10/100 ports (auto-negotiation) reduce switch port requirements
- 1500V AC isolation (between I/O, power, and network ports) and surge/transient protection
- Supports bussed/rail and redundant power
- -40°C to 70°C wide temperature operation
- Withstands 25g shock and 4g vibration
- CE compliant
- UL/cUL Class 1 Div 2 Zone 2 approvals
- ATEX Certified
Specifications
Manuals
Brochure
-
4001 Serial Cables
5-foot ribbon cable, DB25 male and 26-pin female IDC connectors, for 3B/5B backpanel to Ethernet I/O module connection$100Select options -
5020-350: Toroidal AC Current Sensor
- AC Current Sensor to precondition an AC current input signal
- Highly accurate toroidal instrument transformer that converts an AC current signal to a safe, low level, DC milliampere signal (0 to 11.17mA).
$50Select options -
5035 Series: Ethernet Cables
- Ethernet straight cable, CAT5
- Ethernet crossover cable, CAT5E
- Low EMI Double-Shielded Ethernet Patch Cable
$45 – $115Select options -
900EN: 5-Port Ethernet Switch
- 10/100Mbps
- 15 to 36V DC power supply required
- Five shielded RJ-45 sockets, 8-pin, 10Base-T / 100Base-TX
$350Select options -
AMTN, AMTX: ActiveX / .NET Controls for Modbus I/O
- Modbus/TCP or Modbus/RTU
- These ActiveX / .NET software controls provide a fast, easy way to communicate with any Modbus slave devices connected to your PC.
- Get your Visual Basic, Visual C, .NET, Excel, or other compatible applications talking Modbus protocol within minutes.
$270 – $370Select options -
BusWorks XT Connector Kit
DIN rail bus power/excitation connector kit. Includes one DIN rail bus connector (1005-070), one left-side female connector terminal block (1005-220) and one right side male connector terminal block (1005-221).$30Select options -
ESW-MBLIB: Ethernet Modbus C Library Software
- Universal support for five operating systems
- C source code provided
- Demo program included
$0 – $350Select options -
IMC-100A: 10/100BaseTX to 100BaseFX Industrial Media Converter
- UTP to Fiber Media Converter
- RJ45 Port Supports Auto MDI/MDI-X Function
$250Select options -
PS5R: Slim Line Power Supplies
- 10W, 15W, 30W, 60W, 90W, 120W, and 240W models
- Universal Input (85-264V AC / 100-370V DC)
- Lightweight and compact size
$100 – $255Select options -
Terminal Block Replacements
- Simplifies wiring connections on Acromag I/O Modules
- Barrier strip or spring clamp terminal block kits
- Provide safe and secure wiring connections
$35 – $45Select options -
USB Isolator
- USB-powered, USB 2.0 and 1.1 compatible
- 1500V AC / 2100V DC isolation
- No drivers required
$110Select options -
USB-to-Ethernet Adapter
Simplifies configuration of Acromag Ethernet I/O Modules Prevents disruption of existing LANs This device is a USB-to-Ethernet adapter that you can use to communicate with any Acromag Ethernet I/O product for the purpose of setup and re-configuration for your application. It is recommended for initial communication with Acromag Ethernet devices so that you do not have to disrupt your existing network connection.$85Select options -
XT-SIP: Software Interface Package
- Software Interface Package for BusWorks XT Series Ethernet I/O modules.
- Includes configuration software CD-ROM (XT-CONFIG)
- Isolator (USB-Isolator)
- Ethernet cable (5035-360)
- Two USB cables (4001-112, 4001-113)
- Easy setup and digital calibration via USB with Windows configuration software
- Download software only from the Software Tab below
$185Select options
Additional information
Weight | 8 oz |
---|---|
Dimensions | 4.5 × 1.5 × 5 in |
Part Number | XT1231-000: Modbus TCP/IP and i2o protocol, XT1232-000: Ethernet/IP protocol, XT1233-000: Profinet protocol |
Communication | Ethernet/IP, i2o Peer-to-Peer, Modbus TCP/IP, Profinet |
Product Series | BusWorks XT Series |
Configuration | USB Configuration, Windows Software Configuration |
-
Description
The XT1230 offers an isolated Ethernet network interface for up to to sixteen single-ended current input channels. Single-ended inputs enable a higher channel density to save space and a lower cost per channel.
Rugged construction, high density design, and easy USB-to-PC/Windows setup combine for a very effective and reliable module. These units are ideal for remote monitoring, distributed control, or SCADA applications.
Input Ranges:
DC Current:
0 to 11mA, 0 to 20mA, 4 to 20mA, ±20mA
0 to 20 amps AC (with optional AC sensor)
Ethernet Communication:
Modbus TCP/IP, i2o® peer-to-peer available for Modbus TCP/IP only
Ethernet/IP
Profinet
10/100Base-T(X)
PriorityChannel™ device determinism
Power Requirement: 12 to 32V DC (2.8W)Performance Specifications
IMPORTANT: To prevent damage or errors from grounded PCs and surges, Acromag strongly recommends use of the USB-ISOLATOR when configuring an XT1000 I/O module.
USB Interface
USB Connector:
Type: USB Mini-B type socket, 5-pin
Data Rate: 12Mbps. USB v1.1 and 2.0 compatible
Cable Length: 5.0 meters maximum
USB Transient Protection: Transient voltage suppression on power and data lines
Driver: Not required. Uses Windows (HID) driversInput
Accuracy: ±0.05% of span, typical for nominal input ranges
Analog to Digital Converter (A/D): 16-bit Σ-Δ converter. 1.476uA/bit resolution
Noise Rejection: Better than -110dB @ 60Hz
Input Filter Bandwidth: -3dB at 25KHz, typical
Input Conversion Rate: 10ms for all 16 input channels
Input Impedance: 27.4 ohmsEthernet Communication
Protocols:
Modbus TCP/IP, i2o® peer-to-peer available for Modbus TCP/IP only
Ethernet/IP
or Profinet, depending on model number
Ethernet Communication Controller: Innovasic RapID™ Platform with PriorityChannel™ for determinism at the device regardless of network load
Modbus TCP/IP (slave): Port 502 reserved. Supports up to 10 sockets
i2o Peer-to-Peer (master/slave): Can map each of 16 analog input channels separately to output channels. Timed (1-65535 sec) or percent of change updates. Supports GPRS/GSM systems.
Ethernet/IP (adapter): Supports 10 connections. EDS file on website
Profinet (server): Supports 1 connection. GSDML file on website
Connectors: Two shielded 8-pin RJ-45 sockets, 10BaseT/100BaseTX
Wiring: Auto-crossover for MDI or MDI-X
IP Address: User-configurable. 192.168.1.100 default IP address
Data Rate: Auto-negotiated, 10Mbps or 100Mbps
Compliance: IEEE 802.3, 802.3u, 802.3xEnvironmental
Operating temperature: -40 to 70°C (-40 to 158°F)
Storage temperature: -40 to 85°C (-40 to 185°F)
Relative humidity: 5 to 95% non-condensing
MTBF:
463,547 hrs. at 25°C
345,200 hrs. at 40°C
Power Requirement: 12 to 32V DC, 2.8W maximum (113mA maximum @ 24V)
Isolation:
4-way isolation between I/O channels, network (each port), and power
Peak: 1500V AC, ANSI/ISA-82.01-1988
Continuous: 250V AC, 354V DC
Shock and Vibration Immunity:
Vibration: 4g, per IEC 60068-2-64
Shock: 25g, per IEC 60068-2-27
Electromagnetic Compatibility (EMC) Compliance:
Radiated Emissions: BS EN 61000-6-4, CISPR 16
RFI: BS EN 61000-6-2, IEC 61000-4-3
Conducted RFI: BS EN 61000-6-2, IEC 61000-4-6
ESD: BS EN 61000-6-2, IEC 61000-4-2
EFT: BS EN 61000-6-2, IEC 61000-4-4
Surge Immunity: BS EN 61000-6-2, IEC 61000-4-5
Approvals:
CE compliant. UL/cUL Class I; Div. 2 Zone 2. ATEX Cert. II 3 G Ex nA IIC T4 Gc -40°C < Ta < +80°CPhysical
General: General purpose plastic enclosure for mounting on 35mm “T-type” DIN rail
Case Material: Self-extinguishing polyamide, UL94 V-0 rated, color light gray. General purpose NEMA Type 1 enclosure
Circuit Board: Military grade fire-retardant epoxy glass (IPC-4101/98)
I/O Connectors: Removable plug-in type terminal blocks rated for 12A/250V; AWG #26-12, stranded/solid copper wire
Dimensions:
Width = 22.5mm (0.9 inches)
Length = 114.5mm (4.51 inches)
Depth = 99.0mm (3.90 inches)
Shipping Weight: 0.5 pounds (0.22 Kg) packed -
Features & Benefits
- i2o® peer-to-peer available for Modbus TCP/IP only
- i2o® peer-to-peer updates based on change-of-state and/or timed updates
- Easy setup with Windows software via USB
- Low input impendance (27 ohms) reduces loading on current loops
- User-configurable sample averaging (1-200) on a per-channel basis
- 10ms network updates for all 16 input channels
- High-resolution 16-bit Σ∆ A/D converter ensures precise, high accuracy measurements
- High-Density 22.5mm wide package with pluggable, front-facing terminals
- Dual Ethernet 10/100 ports (auto-negotiation) reduce switch port requirements
- 1500V AC isolation (between I/O, power, and network ports) and surge/transient protection
- Supports bussed/rail and redundant power
- -40°C to 70°C wide temperature operation
- Withstands 25g shock and 4g vibration
- CE compliant
- UL/cUL Class 1 Div 2 Zone 2 approvals
- ATEX Certified
-
Tech Papers
How to Connect to Acromag Ethernet I/O Devices Application NoteGetting Connected to Acromag Ethernet I/O Devices These instructions summarize the basic steps you will have to take in order to initially connect an Acromag Ethernet I/O product to your Personal Computer (PC) or laptop. To connect an Ethernet device to your PC, consult with your network administrator and either temporarily change the TCP/IP configuration...How to Communicate with Ethernet XT Profinet from Siemens S7-1200 PLC Application NoteEthernetXT Profinet and Siemens S7-1200 When setting up a Profinet network, Profinet controllers are programmed with a special Profinet Configuration tool, like the Step7 from Siemens. This document illustrates an example procedure for configuring communications between Acromag BusWorks® Series Profinet modules and a Siemens S7-1200 Programmable Controller. It is assumed that the user has a...How to Communicate to Acromag Series Ethernet Modules from Red Lion HMIs Application NoteRed Lion HMIs This document illustrates a procedure for configuring message commands for Acromag Ethernet modules using the Red Lion Crimson 2.0 Software. It is assumed that the user has a working knowledge of the Crimson 2.0 software, as well as a Red Lion HMI. Setting up Communications From a new or existing project, double... -
Specs & Data Sheets
Specifications
Manuals
Brochure
-
Software
Ethernet XT Series Configuration Software (Log in to download the file)Ethernet IP EDS For XTxxx2-000 Modules (Log in to download the file)Profinet GSDML Files for XTxxx3-000 Modules (Log in to download the file)ESW-MBLIB-DEMO (Log in to download the file)AMTN-DEMO (Log in to download the file)ATMX Demo Software (Log in to download the file) -
Accessories
-
4001 Serial Cables
5-foot ribbon cable, DB25 male and 26-pin female IDC connectors, for 3B/5B backpanel to Ethernet I/O module connection$100Select options -
5020-350: Toroidal AC Current Sensor
- AC Current Sensor to precondition an AC current input signal
- Highly accurate toroidal instrument transformer that converts an AC current signal to a safe, low level, DC milliampere signal (0 to 11.17mA).
$50Select options -
5035 Series: Ethernet Cables
- Ethernet straight cable, CAT5
- Ethernet crossover cable, CAT5E
- Low EMI Double-Shielded Ethernet Patch Cable
$45 – $115Select options -
900EN: 5-Port Ethernet Switch
- 10/100Mbps
- 15 to 36V DC power supply required
- Five shielded RJ-45 sockets, 8-pin, 10Base-T / 100Base-TX
$350Select options -
AMTN, AMTX: ActiveX / .NET Controls for Modbus I/O
- Modbus/TCP or Modbus/RTU
- These ActiveX / .NET software controls provide a fast, easy way to communicate with any Modbus slave devices connected to your PC.
- Get your Visual Basic, Visual C, .NET, Excel, or other compatible applications talking Modbus protocol within minutes.
$270 – $370Select options -
BusWorks XT Connector Kit
DIN rail bus power/excitation connector kit. Includes one DIN rail bus connector (1005-070), one left-side female connector terminal block (1005-220) and one right side male connector terminal block (1005-221).$30Select options -
ESW-MBLIB: Ethernet Modbus C Library Software
- Universal support for five operating systems
- C source code provided
- Demo program included
$0 – $350Select options -
IMC-100A: 10/100BaseTX to 100BaseFX Industrial Media Converter
- UTP to Fiber Media Converter
- RJ45 Port Supports Auto MDI/MDI-X Function
$250Select options -
PS5R: Slim Line Power Supplies
- 10W, 15W, 30W, 60W, 90W, 120W, and 240W models
- Universal Input (85-264V AC / 100-370V DC)
- Lightweight and compact size
$100 – $255Select options -
Terminal Block Replacements
- Simplifies wiring connections on Acromag I/O Modules
- Barrier strip or spring clamp terminal block kits
- Provide safe and secure wiring connections
$35 – $45Select options -
USB Isolator
- USB-powered, USB 2.0 and 1.1 compatible
- 1500V AC / 2100V DC isolation
- No drivers required
$110Select options -
USB-to-Ethernet Adapter
Simplifies configuration of Acromag Ethernet I/O Modules Prevents disruption of existing LANs This device is a USB-to-Ethernet adapter that you can use to communicate with any Acromag Ethernet I/O product for the purpose of setup and re-configuration for your application. It is recommended for initial communication with Acromag Ethernet devices so that you do not have to disrupt your existing network connection.$85Select options -
XT-SIP: Software Interface Package
- Software Interface Package for BusWorks XT Series Ethernet I/O modules.
- Includes configuration software CD-ROM (XT-CONFIG)
- Isolator (USB-Isolator)
- Ethernet cable (5035-360)
- Two USB cables (4001-112, 4001-113)
- Easy setup and digital calibration via USB with Windows configuration software
- Download software only from the Software Tab below
$185Select options
-
Additional information
Additional information
Weight 8 oz Dimensions 4.5 × 1.5 × 5 in Part Number XT1231-000: Modbus TCP/IP and i2o protocol, XT1232-000: Ethernet/IP protocol, XT1233-000: Profinet protocol
Communication Ethernet/IP, i2o Peer-to-Peer, Modbus TCP/IP, Profinet
Product Series BusWorks XT Series
Configuration USB Configuration, Windows Software Configuration
Please login to submit this form.