Click to zoom

Please sign in or register to see model options and to add products to your cart.

Product short description:
  • 64-channel single-ended analog voltage input
  • Modbus TCP/IP or UDP/IP communication

These EtherStax I/O modules provide a rugged, high-density, and high-speed solution to interface a large quantity of analog input signals to SCADA and distributed I/O systems. Each unit converts up to 64 single-ended analog voltage signals from various sensors and instruments for transmission to an Ethernet-based control network. Typical applications include process control, automated manufacturing, remote data acquisition, test and measurement, embedded computing, and supervisory monitoring systems.

 

ES2164: Ethernet Analog Input Modules Description

These EtherStax I/O modules provide a rugged, high-density, and high-speed solution to interface a large quantity of analog input signals to SCADA and distributed I/O systems. Each unit converts up to 64 single-ended analog voltage signals from various sensors and instruments for transmission to an Ethernet-based control network. Typical applications include process control, automated manufacturing, remote data acquisition, test and measurement, embedded computing, and supervisory monitoring systems.

EtherStax units are built and tested to deliver high reliability and dependable performance in hostile environments. Many features help increase reliability, improve performance and protect from harsh environments. Available in an aluminum enclosure or as an open circuit board, both formats stack vertically to maintain a very small footprint.

Performance Specifications

Analog Field Inputs

Input Channel Configuration:
64 single-ended analog inputs.
32 channels on front and rear panels of unit.

DC Voltage Input Ranges (per-channel basis):
±5V or ±10V DC (default).
User-configured on a per-channel basis.

Input Scaling: Floating Point Format:
IEEE-754 32-bit configurable for 12 digits with 4 decimal places.
16-bit Signed Integer Format: All channels represented as ±30,000.

Input Resolution and Accuracy:
Resolution: 16-bit maximum, 0.00167%.
Accuracy: Better than 0.05% of range.

Input Impedance: Greater than 1M ohms.

Input Scan Groups and Scan Times:
Eight user-enabled 8-channel scan groups.
10mS (100Hz) update of all 64 channels.
First 8-channel group updates in 1.80mS (555Hz). Each additional 8-channel group adds 1.20mS to the update time.

Sample Averaging: 0 to 500 samples, user-configurable.

Input Overvoltage Protection: Bipolar Transient Voltage Suppressors (TVS), 14V working voltage.

Noise Rejection: Common Mode (50-60Hz): Better than 72dB.

Local Alarm Output

Configuration: Failsafe or non-failsafe (software-configurable) relay trips on power or link-loss failure.

Type: SPST-NO, 1 Form A, Class I, Division II approved.

Rating:
5A @ 24V DC/250V AC, 6000 cycles resistive.
3A @ 24V DC/250V AC, 100,000 cycles general.
2A @ 24V DC/250V AC, hazardous locations.

Maximum Switching Voltage and Power: 250V AC / 750VA, 125V DC / 90W.

Ethernet Interface

Internal Switch or Hub/Repeater:
Dual-port Ethernet switch.
Web-configurable as a true switch (default mode) or low-latency hub.

Network Connector (10/100 Base-TX Copper):
One or two 8-pin RJ-45 connectors.
Automatic MDI/MDI-X.
100m communication distance.

Network Connector (100 Base-FX Fiber-optic):
One multi-mode duplex SC connector.
Full-duplex only.
2km communication distance.

Protocols and Addressing:
Modbus TCP/IP or UDP/IP.
StaticIP, DHCP, BootP.
Configurable IP addresses.

Ethernet Modbus TCP/IP Sockets/Sessions: 1-10 socket/sessions programmable via web page.

Ethernet Redundancy: Compatible with STP, RSTP, proprietary schemes.

Environmental

Operating and Storage Temperature:
Operating Range: -40 to 70°C (-40 to 158°F).
Storage Range: -40 to 85°C (-40 to 185°F).

Power Requirements:
18-36V DC. Redundant, diode-coupled terminals.
4.4W (copper ports), 5.5W (fiber-optic ports).

Ambient Temperature Effect: Less than 25ppm/°C (0.0025%/°C).

Isolation:
I/O, power, relay and Ethernet port-to-port.
Peak: 1500V AC, ANSI/ISA-82.01-1988.
Continuous: 250V AC, 354V DC.

Enclosure and Physical

Housing Classification and Dimensions:
IP20: 8.226” x 2.444” x 7.25”, 4 lbs. packed.
PCB: 7.920” x 1.875” x 7.25”, 1.65 lbs. packed.

Safety Approvals:
UL/cUL Listed.
Hazardous Locations: Class I; Division 2; A, B, C, D.
Open board units: UL Recognized.

Shock and Vibration Immunity (in enclosure):
Mechanical Shock: 50g (3ms), 30g (11ms).
Random Vibration: 5g, (5-500Hz).

 

  • 64 single-ended analog voltage inputs
  • 4-way isolation and surge suppression
  • High-resolution 16-bit A/D
  • High-speed scanning with 10 millisecond update of all 64 channels
  • Automatic zero/span calibration
  • On-demand self-test verifies calibration
  • Configurable from any web browser
  • User-configurable sample averaging and integration/totalization function with non-volatile registers
  • Dual-format data registers support 16-bit integers or 32-bit floating point
  • Scaling registers on all channels
  • Operating temperature: -40 to 70°C (-40 to 158°F)

 

How to Communicate with Modbus/TCP Modules from Ignition Software - 8501121
Setting Up and Communicating with Acromag Series 9xxEN-40xx and XTxxx1-xxx Modbus/TCP Modules and EtherStax™ Modbus/TCP from Ignition Software This document illustrates a procedure for configuring OPC tags intended for Acromag BusWorks® Series Modbus/TCP modules using Windows software from Inductive Automation. It is assumed that the user has a working knowledge of OPC, Modbus TCP, and...
How to Configure LabVIEW to Communicate with Modbus I/O Modules Via an OPC Server - 8500881
Configuring LabVIEW 2009 to Communicate with Acromag BusWorks and EtherStax Modbus I/O Modules via an OPC Server Introduction National Instruments™ LabVIEW can be used to monitor and control Acromag BusWorks ® and EtherStax ® Modbus I/O modules via an OPC server. A separate application note, Configuring Kepware KEPServerEX® 5.0 for communications with Acromag BusWorks and EtherStax...
How to Communicate to Ethernet Modules from Red Lion HMIs - 8500874
How to Communicate to Acromag Ethernet Modules from Red Lion HMIs Red Lion HMIs This document illustrates a procedure for configuring message commands for Acromag Ethernet modules using the Red Lion Crimson 2.0 software. It is assumed that the user has a working knowledge of the Crimson 2.0 software, as well as a Red Lion...

Manuals

ES2163 / ES2164 User Manual (Log in to download the file)

AMTN-DEMO (Log in to download the file)
ATMX Demo Software (Log in to download the file)
ESW-MBLIB-DEMO (Log in to download the file)
Ethernet IP EDS For XTxxx2-000 Modules (Log in to download the file)
EtherStax Modbus Copy Utility Software (Log in to download the file)
  • Compare

    20RM-16-DIN: 19” rack-mount kit with DIN rail

    • 19" rack-mount kit with DIN rail
    Select options
  • Compare

    4001 Serial Cables

    5-foot ribbon cable, DB25 male and 26-pin female IDC connectors, for 3B/5B backpanel to Ethernet I/O module connection
    Select options
  • Compare

    5020-350: Toroidal AC Current Sensor

    • AC Current Sensor to precondition an AC current input signal
    • Highly accurate toroidal instrument transformer that converts an AC current signal to a safe, low level, DC milliampere signal (0 to 11.17mA).
    Select options
  • Compare

    5035 Series: Ethernet Cables

    • Ethernet straight cable, CAT5
    • Ethernet crossover cable, CAT5E
    • Low EMI Double-Shielded Ethernet Patch Cable
    Select options
  • Compare

    900EN: 5-Port Ethernet Switch

    • 10/100Mbps
    • 15 to 36V DC power supply required
    • Five shielded RJ-45 sockets, 8-pin, 10Base-T / 100Base-TX
    Acromag’s five-port Ethernet switch is specially designed for use in industrial applications. Rugged construction and a variety of security features ensure reliable operation under demanding conditions.
    Select options
  • Compare

    AMTN, AMTX: ActiveX / .NET Controls for Modbus I/O

    • Modbus/TCP or Modbus/RTU
    • These ActiveX / .NET software controls provide a fast, easy way to communicate with any Modbus slave devices connected to your PC.
    • Get your Visual Basic, Visual C, .NET, Excel, or other compatible applications talking Modbus protocol within minutes.
    Select options
  • Compare

    DIN Rail: Type T

    • DIN Rail Strip, Type T
    Select options
  • Compare

    ESW-MBLIB: Ethernet Modbus C Library Software

    • Universal support for five operating systems
    • C source code provided
    • Demo program included
    Select options
  • Compare

    EtherStax Mounting Kits

    • EtherStax mounting accessories
    Select options
  • Compare

    IMC-100A: 10/100BaseTX to 100BaseFX Industrial Media Converter

    • UTP to Fiber Media Converter
    • RJ45 Port Supports Auto MDI/MDI-X Function
     
    Select options
  • Compare

    PS5R: Slim Line Power Supplies

    • 10W, 15W, 30W, 60W, 90W, 120W, and 240W models
    • Universal Input (85-264V AC / 100-370V DC)
    • Lightweight and compact size
     
    Select options
  • Compare

    Terminal Block Replacements

    • Simplifies wiring connections on Acromag I/O Modules
    • Barrier strip or spring clamp terminal block kits
    • Provide safe and secure wiring connections
    Select options
  • Compare

    USB-to-Ethernet Adapter

    Simplifies configuration of Acromag Ethernet I/O Modules Prevents disruption of existing LANs This device is a USB-to-Ethernet adapter that you can use to communicate with any Acromag Ethernet I/O product for the purpose of setup and re-configuration for your application. It is recommended for initial communication with Acromag Ethernet devices so that you do not have to disrupt your existing network connection.
    Select options

Additional information

Weight 80 oz
Dimensions 9 × 2.5 × 7.25 in
Part Number

ES2164-0000: 2 Cu ports, IP20 enclosure, ES2164-0010: 2 Cu ports, open PC board, ES2164-1000: 1 Cu port and 1 fiber port, IP20 enclosure, ES2164-1010: 1 Cu port and 1 fiber port, open PC board

Communication

i2o Peer-to-Peer, Modbus TCP/IP, Modbus UDP/IP

Product Series

EtherStax Series

  • Description

    ES2164: Ethernet Analog Input Modules Description

    These EtherStax I/O modules provide a rugged, high-density, and high-speed solution to interface a large quantity of analog input signals to SCADA and distributed I/O systems. Each unit converts up to 64 single-ended analog voltage signals from various sensors and instruments for transmission to an Ethernet-based control network. Typical applications include process control, automated manufacturing, remote data acquisition, test and measurement, embedded computing, and supervisory monitoring systems.

    EtherStax units are built and tested to deliver high reliability and dependable performance in hostile environments. Many features help increase reliability, improve performance and protect from harsh environments. Available in an aluminum enclosure or as an open circuit board, both formats stack vertically to maintain a very small footprint.

    Performance Specifications

    Analog Field Inputs

    Input Channel Configuration:
    64 single-ended analog inputs.
    32 channels on front and rear panels of unit.

    DC Voltage Input Ranges (per-channel basis):
    ±5V or ±10V DC (default).
    User-configured on a per-channel basis.

    Input Scaling: Floating Point Format:
    IEEE-754 32-bit configurable for 12 digits with 4 decimal places.
    16-bit Signed Integer Format: All channels represented as ±30,000.

    Input Resolution and Accuracy:
    Resolution: 16-bit maximum, 0.00167%.
    Accuracy: Better than 0.05% of range.

    Input Impedance: Greater than 1M ohms.

    Input Scan Groups and Scan Times:
    Eight user-enabled 8-channel scan groups.
    10mS (100Hz) update of all 64 channels.
    First 8-channel group updates in 1.80mS (555Hz). Each additional 8-channel group adds 1.20mS to the update time.

    Sample Averaging: 0 to 500 samples, user-configurable.

    Input Overvoltage Protection: Bipolar Transient Voltage Suppressors (TVS), 14V working voltage.

    Noise Rejection: Common Mode (50-60Hz): Better than 72dB.

    Local Alarm Output

    Configuration: Failsafe or non-failsafe (software-configurable) relay trips on power or link-loss failure.

    Type: SPST-NO, 1 Form A, Class I, Division II approved.

    Rating:
    5A @ 24V DC/250V AC, 6000 cycles resistive.
    3A @ 24V DC/250V AC, 100,000 cycles general.
    2A @ 24V DC/250V AC, hazardous locations.

    Maximum Switching Voltage and Power: 250V AC / 750VA, 125V DC / 90W.

    Ethernet Interface

    Internal Switch or Hub/Repeater:
    Dual-port Ethernet switch.
    Web-configurable as a true switch (default mode) or low-latency hub.

    Network Connector (10/100 Base-TX Copper):
    One or two 8-pin RJ-45 connectors.
    Automatic MDI/MDI-X.
    100m communication distance.

    Network Connector (100 Base-FX Fiber-optic):
    One multi-mode duplex SC connector.
    Full-duplex only.
    2km communication distance.

    Protocols and Addressing:
    Modbus TCP/IP or UDP/IP.
    StaticIP, DHCP, BootP.
    Configurable IP addresses.

    Ethernet Modbus TCP/IP Sockets/Sessions: 1-10 socket/sessions programmable via web page.

    Ethernet Redundancy: Compatible with STP, RSTP, proprietary schemes.

    Environmental

    Operating and Storage Temperature:
    Operating Range: -40 to 70°C (-40 to 158°F).
    Storage Range: -40 to 85°C (-40 to 185°F).

    Power Requirements:
    18-36V DC. Redundant, diode-coupled terminals.
    4.4W (copper ports), 5.5W (fiber-optic ports).

    Ambient Temperature Effect: Less than 25ppm/°C (0.0025%/°C).

    Isolation:
    I/O, power, relay and Ethernet port-to-port.
    Peak: 1500V AC, ANSI/ISA-82.01-1988.
    Continuous: 250V AC, 354V DC.

    Enclosure and Physical

    Housing Classification and Dimensions:
    IP20: 8.226” x 2.444” x 7.25”, 4 lbs. packed.
    PCB: 7.920” x 1.875” x 7.25”, 1.65 lbs. packed.

    Safety Approvals:
    UL/cUL Listed.
    Hazardous Locations: Class I; Division 2; A, B, C, D.
    Open board units: UL Recognized.

    Shock and Vibration Immunity (in enclosure):
    Mechanical Shock: 50g (3ms), 30g (11ms).
    Random Vibration: 5g, (5-500Hz).

     

  • Features & Benefits

    • 64 single-ended analog voltage inputs
    • 4-way isolation and surge suppression
    • High-resolution 16-bit A/D
    • High-speed scanning with 10 millisecond update of all 64 channels
    • Automatic zero/span calibration
    • On-demand self-test verifies calibration
    • Configurable from any web browser
    • User-configurable sample averaging and integration/totalization function with non-volatile registers
    • Dual-format data registers support 16-bit integers or 32-bit floating point
    • Scaling registers on all channels
    • Operating temperature: -40 to 70°C (-40 to 158°F)

     

  • Tech Papers

    How to Communicate with Modbus/TCP Modules from Ignition Software - 8501121
    Setting Up and Communicating with Acromag Series 9xxEN-40xx and XTxxx1-xxx Modbus/TCP Modules and EtherStax™ Modbus/TCP from Ignition Software This document illustrates a procedure for configuring OPC tags intended for Acromag BusWorks® Series Modbus/TCP modules using Windows software from Inductive Automation. It is assumed that the user has a working knowledge of OPC, Modbus TCP, and...
    How to Configure LabVIEW to Communicate with Modbus I/O Modules Via an OPC Server - 8500881
    Configuring LabVIEW 2009 to Communicate with Acromag BusWorks and EtherStax Modbus I/O Modules via an OPC Server Introduction National Instruments™ LabVIEW can be used to monitor and control Acromag BusWorks ® and EtherStax ® Modbus I/O modules via an OPC server. A separate application note, Configuring Kepware KEPServerEX® 5.0 for communications with Acromag BusWorks and EtherStax...
    How to Communicate to Ethernet Modules from Red Lion HMIs - 8500874
    How to Communicate to Acromag Ethernet Modules from Red Lion HMIs Red Lion HMIs This document illustrates a procedure for configuring message commands for Acromag Ethernet modules using the Red Lion Crimson 2.0 software. It is assumed that the user has a working knowledge of the Crimson 2.0 software, as well as a Red Lion...
  • Specs & Data Sheets

    Manuals

    ES2163 / ES2164 User Manual (Log in to download the file)

  • Software

    AMTN-DEMO (Log in to download the file)
    ATMX Demo Software (Log in to download the file)
    ESW-MBLIB-DEMO (Log in to download the file)
    Ethernet IP EDS For XTxxx2-000 Modules (Log in to download the file)
    EtherStax Modbus Copy Utility Software (Log in to download the file)
  • Accessories

    • Compare

      20RM-16-DIN: 19” rack-mount kit with DIN rail

      • 19" rack-mount kit with DIN rail
      Select options
    • Compare

      4001 Serial Cables

      5-foot ribbon cable, DB25 male and 26-pin female IDC connectors, for 3B/5B backpanel to Ethernet I/O module connection
      Select options
    • Compare

      5020-350: Toroidal AC Current Sensor

      • AC Current Sensor to precondition an AC current input signal
      • Highly accurate toroidal instrument transformer that converts an AC current signal to a safe, low level, DC milliampere signal (0 to 11.17mA).
      Select options
    • Compare

      5035 Series: Ethernet Cables

      • Ethernet straight cable, CAT5
      • Ethernet crossover cable, CAT5E
      • Low EMI Double-Shielded Ethernet Patch Cable
      Select options
    • Compare

      900EN: 5-Port Ethernet Switch

      • 10/100Mbps
      • 15 to 36V DC power supply required
      • Five shielded RJ-45 sockets, 8-pin, 10Base-T / 100Base-TX
      Acromag’s five-port Ethernet switch is specially designed for use in industrial applications. Rugged construction and a variety of security features ensure reliable operation under demanding conditions.
      Select options
    • Compare

      AMTN, AMTX: ActiveX / .NET Controls for Modbus I/O

      • Modbus/TCP or Modbus/RTU
      • These ActiveX / .NET software controls provide a fast, easy way to communicate with any Modbus slave devices connected to your PC.
      • Get your Visual Basic, Visual C, .NET, Excel, or other compatible applications talking Modbus protocol within minutes.
      Select options
    • Compare

      DIN Rail: Type T

      • DIN Rail Strip, Type T
      Select options
    • Compare

      ESW-MBLIB: Ethernet Modbus C Library Software

      • Universal support for five operating systems
      • C source code provided
      • Demo program included
      Select options
    • Compare

      EtherStax Mounting Kits

      • EtherStax mounting accessories
      Select options
    • Compare

      IMC-100A: 10/100BaseTX to 100BaseFX Industrial Media Converter

      • UTP to Fiber Media Converter
      • RJ45 Port Supports Auto MDI/MDI-X Function
       
      Select options
    • Compare

      PS5R: Slim Line Power Supplies

      • 10W, 15W, 30W, 60W, 90W, 120W, and 240W models
      • Universal Input (85-264V AC / 100-370V DC)
      • Lightweight and compact size
       
      Select options
    • Compare

      Terminal Block Replacements

      • Simplifies wiring connections on Acromag I/O Modules
      • Barrier strip or spring clamp terminal block kits
      • Provide safe and secure wiring connections
      Select options
    • Compare

      USB-to-Ethernet Adapter

      Simplifies configuration of Acromag Ethernet I/O Modules Prevents disruption of existing LANs This device is a USB-to-Ethernet adapter that you can use to communicate with any Acromag Ethernet I/O product for the purpose of setup and re-configuration for your application. It is recommended for initial communication with Acromag Ethernet devices so that you do not have to disrupt your existing network connection.
      Select options
  • Additional information

    Additional information

    Weight 80 oz
    Dimensions 9 × 2.5 × 7.25 in
    Part Number

    ES2164-0000: 2 Cu ports, IP20 enclosure, ES2164-0010: 2 Cu ports, open PC board, ES2164-1000: 1 Cu port and 1 fiber port, IP20 enclosure, ES2164-1010: 1 Cu port and 1 fiber port, open PC board

    Communication

    i2o Peer-to-Peer, Modbus TCP/IP, Modbus UDP/IP

    Product Series

    EtherStax Series