Click to zoom
$125$140
Clear
Product short description:
  • Bluetooth® wireless configuration
  • Two alarm relay outputs
  • 0/4-20mA and 0/1-5V transmitter output

uBTA-P-1MR: Single channel transmitter/alarm, mechanical relays
uBTA-P-1SR: Single channel transmitter/alarm, solid-state relays

Click here to watch a short AcroMaggie video highlighting the features of the microBlox Series.

[DISPLAY_ULTIMATE_PLUS]

Models

uBTA-P-1MR: Single channel transmitter/alarm, mechanical relays
uBTA-P-1SR: Single channel transmitter/alarm, solid-state relays

The uBTA carriers are used with Acromag’s microBlox® signal conditioning modules to create powerful alarms that also provide a voltage/current transmitter output. The plug-in modules offer the convenience of wireless field programming on a smartphone or tablet.

The microBlox uB modules offer a flexible space-saving solution for isolating, monitoring, and converting industrial sensor signals to interface with your data acquisition or control system. By inserting a uB input module into the carrier, you get a device with both alarm and transmitter capabilities. With a broad selection of uB input modules, you can monitor many different signal types by simply interchanging modules on the carrier.

Plug-in modules measure current, voltage, thermocouple, or RTD input. Carriers produce a process current and voltage output signal and trip alarm relays if high or low limits are exceeded. Each alarm carrier has two independent relay contacts (either mechanical or solid-state).

Bluetooth® wireless technology enables configuration using an Android™ or iOS® mobile device. Acromag’s Agility™ app helps you quickly set input/output ranges and scaling to your specific requirements. It is also fast and easy to configure your alarm setpoints. You can define two high limits, low limits, or window alarms for each relay.

These rugged carriers are well-suited for use in harsh industrial environments. Carriers mount on T-type DIN rails for high-density installation. They have high immunity to noise, surges, shock, vibration, and extreme temperatures. Installation in hazardous locations is also supported with compliance to CE, ATEX, and UL regulations.

Performance Specifications

Analog Field Input

Field Range: See specs for the specific plug-in uB module used.

Alarm Relay Output

Relay: Two independent relays. Each relay may have its own set-point, dead-band and reverse acting status setting.
Models: uBTA-P-1MR: Type: Dual 1 FORM C, (SPDT, normally open and normally closed) mech. relays. 5A, 250V AC, 30V DC
Models: uBTA-P-1SR: Type: Dual 1 FORM A, (SPST, normally open) solid-state relays. 1A, 200V peak AC/DC

Transmitter Output

Simultaneous 0 to 5V / 1 to 5V, 0 to 20mA / 4 to 20mA

General

Power: Connect 6-32V DC SELV (Safety Extra Low Voltage), up to 1.8W including modules. Current draw will be dependent on carrier model, relay type, whether you utilize the transmitter output, your plug-in module, and your voltage level. See manual for more information.
Accuracy: Better than ±0.1%. typical

Physical

Dimensions:
Width: 2.66” (67.6 mm)
Height: 2.83” (72.0 mm)
Depth: 1.42” (36.0 mm) without modules, 2.8” ( 71 mm) with uB module
Weight: 0.25 lbs. (0.114 Kg)
I/O Connectors: Fixed type terminal blocks rated for 5A/250V; AWG #28-16, stranded or solid copper wire.
Case: Self-extinguishing polyamide, UL94 V-0 rated, color light gray. General purpose NEMA Type 1 enclosure.
Circuit Board: Military grade fire-retardant epoxy glass per IPC-4101/98
DIN-Rail Mounting: T-type DIN rails

Environmental

Operating Temperature: -40 to 75°C (-40° to 158°F)
Storage Temperature: -40 to 85°C (-40° to 185°F)
Relative Humidity: 5 to 95% non-condensing
Emissions: Class B product with emissions per BS EN 61000-6-4
Approvals: CE compliant. Designed for UL/cUL Class I Division 2 Groups ABCD, ATEX / IECEx Zone 2

  • Dual alarms (hi/hi, lo/lo, hi/lo) with two independent mechanical or solid-state relays
  • Mechanical relays switch 5A at 250V AC, 30V DC
  • Transmitter output with scalable 0-20mA, 4-20mA, and 0-5V signal ranges
  • Interchangeable input modules for measuring a wide variety of signal types
  • Easy configuration using Bluetooth wireless technology with smartphone or tablet running Acromag Agility app for Android® and iOS®
  • Rugged design for use in harsh environments
  • High accuracy alarm and transmitter output
  • High noise immunity and stability
  • High voltage isolation between input, output, relay contacts, and power
  • All I/O and power ports transient-protected
  • Wide -40 to 75°C operating range
  • CE compliant. UL/cUL Class I Div 2, ATEX / IECEx Zone 2 approvals

Specifications

Manuals

uBTA-P-1MR and uBTA-P-1SR User Manual (Log in to download the file)

microBlox Reconfiguration User Manual (Log in to download the file)

microBlox Series Overview User Manual (Log in to download the file)

Agility™ Config Tool (Wireless) (Log in to download the file)

Additional information

Weight 16 oz
Dimensions 13 × 12 × 3 in
Part Number

uB42-B: Input: Configurable 0-20mA w/EXC, 100Hz, Configurable ±5V, uB42-01: Input: 4-20mA w/ 2-W EXC, 100Hz, Output: 0-5V, uB42-02: Input: 4-20mA w/ 2-W EXC, 100Hz, Output: 1-5V

Configuration

Agility Mobile App, Wireless Configuration

Product Series

microBlox Series

  • Description

    Field Input: 0-20mA or 4-20mA DC ranges
    Host Output: 0-5V, 1-5V or ±5V ranges

    Acromag’s microBlox® uB Series I/O modules offer a compact, high-performance solution for interfacing sensors and field devices with data acquisition systems. uB signal conditioning modules are ideal to isolate, filter, convert and amplify a wide variety of signal types for test, measurement and control systems. Just plug uB modules into 4, 8, or 16-channel backpanels in any mix for a high-density analog I/O interface. Channel-to-channel isolation provides optimal noise and surge protection from ground loops, spikes, and high common mode voltages.

    The uB42 model conditions and converts a DC process current field input signal from a 2-wire transmitter to a scaled 0-5V or ±5V output. It provides field excitation (12V/22mA) for the transmitter and is useful to isolate non-isolated transmitters. This module can also interface AC current signals with the model 5020-350 toroid sensor producing a 0 to 11.17mA input.

    Bluetooth® wireless technology versions enable configuration using a smart phone or tablet. Acromag’s Agility™ app, available for Android™ and iOS® mobile devices, helps you vary input/output ranges and scaling to your specific application. The Agility app can also set an alarm output function with a setpoint limit and deadband. Other app functions include polling inputs, trending values in a shareable chart, updating calibration, and diagnostic troubleshooting.

    Backpanels provide power, I/O wiring terminals, and host access to an industry-standard analog signal bus. Modules are hot-swappable without screws. Data acquisition boards can access all host I/O signals on the DB25 bus connector.

    Performance Specifications

    See Backpanels for additional system specifications.

    Field Input

    Field Range:
    Fixed ranges: 0-20mA or 4-20mA
    User-configurable -B models: 0-20mA DC
    Resolution:
    16-bit ADC. 4-20mA: 1/24319. 0-20mA: 1/30399
    When used with AC Current Sensor 5020-350: 1/16978 for 0-11.17mA range
    Resistance: 47.5Ω ±0.1%. Input shunt to ground or loop load.
    Excitation: +13V loop power supply. 12V to transmitter and 1V for internal input shunt resistor.
    Input Sample Rate: 1200sps
    Normal Mode (Bandwidth): -3dB at 100Hz, 180Hz typical
    Protection: TVS & diode clamps built-in plus additional protection on back-panel.
    Common Mode Rejection: 130dB typical, 50-60Hz

    Host Output

    Host Range:
    uB42-01: 0-5V. uB42-02: 1-5V. uB42-03: 0-5V
    uB42-B: User-configurable ±5V
    Resolution:
    16-bit DAC. 0-5V: 1/26305. ±5VDC: 1/52610
    1-5V: 1/21044
    Drive Capability: 5V into 1KΩ minimum or 5mA maximum load
    Response Time: Output Steps 0-98% in 6ms, typical

    General

    Power Consumption: 0.25W max. with no excitation load, 0.6W max. or 120mA from 5V with 20mA excitation load.
    I/O Resolution:
    Effective resolution is the least of input (A/D) and output (D/A) resolution with 0-20mA/0-5V: 1/30399
    4-20mA/1-5V 1/21044
    0-11.17mA/0-5V: 1/16978
    Accuracy:
    Better than ±0.1%. 0.05% typical
    Non-Linearity: Better than ±0.05%, typical
    Noise:
    Less than 0.06% of span p-p, rms
    Ambient Effect:
    Less than ±80ppm/°C
    Dimensions:
    Height: 1.380” with connectors. 0.970” without
    Width: 0.425”
    Length: 1.425”

    Environmental

    Operating Temperature: -40 to 80°C (-40° to 176°F)
    Storage Temperature: -40 to 85°C (-40° to 185°F)
    Relative Humidity: 0 to 95% non-condensing
    Power Requirement: 5V powered,10-32V power optional (requires uBDC-1 power module & backpanel)
    Safety Isolation:
    Field channels are individually isolated field channel-to-field channel and from the field to the host I/O bus (host group includes 5V power) for common-mode voltages up to 250V AC, or 354V DC off DC power ground, on a continuous basis (will withstand 1500VAC HIPOT/dielectric strength test for one minute without breakdown). This complies with test requirements of ANSI/ISA-82.01-1988 for voltage rating specified.
    Shock and Vibration Immunity:
    Conforms to:
    IEC 60068-2-6: 10-500 Hz, 4G, 2 hours/axis, for sinusoidal vibration.
    IEC 60068-2-64: 10-500 Hz, 4G-rms, 2 hours/axis, for random vibration.
    EC 60068-2-27: 25G, 11ms half-sine, 18 shocks at 6 orientations, for mechanical shock.
    Electromagnetic Compatibility (EMC) Compliance:
    Minimum immunity per BS EN 61000-6-1 (2007):
    CE marked, per EMC Directive 2004/108/EC. Electrostatic Discharge Immunity (ESD), per IEC 61000-4-2
    Radiated Field Immunity (RFI), per IEC 61000-4-4
    Electrical Fast Transient Immunity (EFT), per IEC 61000-4-4
    Surge Immunity, per IEC 61000-4-5
    Conducted RF Immunity (CRFI), per IEC 61000-4-6
    Emissions
    Class B product with emissions per BS EN 61000-6-3 (2007+A1:2011): enclosure port, per CISPR 16
    Low voltage AC mains port, per CISPR 16
    Approvals
    CE compliant. RoHS Compliant
    UL/cUL Class 1, Division 2, Groups ABCD
    ATEX Zone 2

  • Features & Benefits

    • Dual alarms (hi/hi, lo/lo, hi/lo) with two independent mechanical or solid-state relays
    • Mechanical relays switch 5A at 250V AC, 30V DC
    • Transmitter output with scalable 0-20mA, 4-20mA, and 0-5V signal ranges
    • Interchangeable input modules for measuring a wide variety of signal types
    • Easy configuration using Bluetooth wireless technology with smartphone or tablet running Acromag Agility app for Android® and iOS®
    • Rugged design for use in harsh environments
    • High accuracy alarm and transmitter output
    • High noise immunity and stability
    • High voltage isolation between input, output, relay contacts, and power
    • All I/O and power ports transient-protected
    • Wide -40 to 75°C operating range
    • CE compliant. UL/cUL Class I Div 2, ATEX / IECEx Zone 2 approvals
  • Specs & Data Sheets

    Specifications

    Manuals

    uBTA-P-1MR and uBTA-P-1SR User Manual (Log in to download the file)

    microBlox Reconfiguration User Manual (Log in to download the file)

    microBlox Series Overview User Manual (Log in to download the file)

  • Software

    Agility™ Config Tool (Wireless) (Log in to download the file)
  • Accessories

  • Additional information

    Additional information

    Weight 16 oz
    Dimensions 13 × 12 × 3 in
    Part Number

    uB42-B: Input: Configurable 0-20mA w/EXC, 100Hz, Configurable ±5V, uB42-01: Input: 4-20mA w/ 2-W EXC, 100Hz, Output: 0-5V, uB42-02: Input: 4-20mA w/ 2-W EXC, 100Hz, Output: 1-5V

    Configuration

    Agility Mobile App, Wireless Configuration

    Product Series

    microBlox Series