Description

These modules provide an isolated Profibus-DP network interface for six analog input channels. Differential inputs eliminate ground loops and thus the need for isolators in any applications. Multi-range inputs accept signals from a variety of sensor and devices. High-resolution, low noise, A/D converters deliver high accuracy and reliability.

Input Ranges

DC Current (user-selectable ranges) 0 to 1mA, 0 to 11mA, 0 to 20mA, 4 to 20mA 0 to 20 amps AC (with optional AC sensor) DC Voltage (user-selectable ranges) ±78mV to ±10V DC (eight range options)

Network Communication

Profibus-DP, RS-485 network up to 12Mbaud

Power Requirement

12 to 36V DC supply required

Approvals

Profibus PNO certified. CE marked. UL, cUL listed. Class I; Division 2; Groups A, B, C, D

Performance

Input

Configuration: Input ranges are selectable for a 3-channel group. Accuracy: Better than ±0.05% of span for nominal input ranges. Analog to Digital Converter (A/D): 16-bit A/D converter Resolution: 0.005% or 1 part in 20000 Noise Rejection: Normal Mode: Better than 40dB @ 60Hz Common Mode: Better than 140dB @ 60Hz Input Filter Bandwidth: -3dB at 3Hz, typical DC Current Input Impedance: 24.9 ohms DC Voltage Input Impedance: Greater than 110.5K ohms

Environmental

Ambient Temperature: Operating: -25 to 70°C (-13 to 158°F) Storage: -40 to 85°C (-40 to 185°F) Relative Humidity: 5 to 95%, non-condensing Isolation: 1500V AC for 60 seconds or 250V AC continuous 3-way isolation between I/O, network, and power

Showing all 7 results

  • Compare

    961PB, 962PB: 6-Channel Differential Profibus-DP Input Modules

    • DC Current or DC Voltage Signals
    • 6 input channels, 0 to 20mA in 3 selectable ranges (0 to 20 amps AC with optinal AC sensor) or ±78mV to ±10V DC with eight range options
    • 12 to 36V DC power
    • Profibus-DP, RS-485 network up to 12Mbaud
    $510
    Select options
  • Compare

    963PB, 964PB: 12-Channel Single-Ended Input Profibus-DP Modules

    • DC Current or DC Voltage Signals
    • 12 input channels, 0 to 20mA in 3 selectable ranges (0 to 20 amps AC with optinal AC sensor) or ±1V, ±5V or ±10V DC
    • 12 to 36V DC power
    • Profibus-DP, RS-485 network up to 12Mbaud
    $585
    Select options
  • Compare

    965PB: 4 or 6-Channel Input Profibus-DP Modules

    • Thermocouple or Millivolt Signals
    • 4 or 6 input channels, thermocouple or DC millivolts (user-selectable)
    • 12 to 36V DC  power
    • Profibus-DP, RS-485 network up to 12Mbaud
    $540$620
    Select options
  • Compare

    966PB: 4 or 6-Channel Input Profibus-DP Modules

    • RTD or Resistance Signals
    • 4 or 6 input channels, Platinum 100 ohm, Nickel 120 ohm, Copper 10 ohm; 0 to 500 ohms resistance
    • 12 to 36V DC power
    • Profibus-DP, RS-485 network up to 12Mbaud
    $540$620
    Select options
  • Compare

    972PB, 973PB: 4 or 6-Channel Output: DC Current or DC Voltage Signals

    • 0 to 1mA, 0 to 20mA, or 4 to 20mA DC Current Output; 0 to 1V, 0 to 5V or 0 to 10V DC Output
    • 12 to 36V DC Power
    • Profibus-DP, RS-485 network up to 12Mbaud
    $540$620
    Select options
  • Compare

    981PB, 982PB, 983PB: Profibus-DP 12-Channel Digital I/O

    • Active-Low Inputs, Sinking Outputs
    • 12 input channels, 0 to 35V DC range
    • 12 to 36V DC
    • High-speed RS-485
    $360$385
    Select options
  • Compare

    Profibus-DP GSD Files

    • Download GSD files from the Software Tab
    Read more